At the current time, the Supermicro® SuperBlade® is shipping with power supplies of 1620 Watts or larger. In order to supply adequate power for the SuperBlade system, your site should provide 30 Amps of 200-240V power for every pair of power supplies that are installed in your SuperBlade chassis.
Although the Power Distribution Unit (Figure 3) that is recommended by Supermicro supports up to four power connections, only two connections should be made to each PDU. The PDU has a Nema L6-30 connector plug that can plug into a Nema l6-30 socket (Figure 4). Each PDU, supporting two power supplies must be plugged into a separate circuit that provides 30 Amps of power and a voltage ranging from 200-240V.
Table 1 below illustrates the various Power Supplies offered by Supermicro.

As this table illustrates, the 2000 Watt power supply can draw up to 13.6 Amps. So that for a single 30 Amp circuit supplying a PDU, no more than 2 power supplies may be connected to the PDU.
Supermicro SuperBlade® productincludes a power extension cord CBL-0223L for 2500/2000W (Figure 1) or CBL-0248L for 1400W/1620W (Figure 2) system. The power cord typically connects the power supply to a Power Distribution Unit (Figure 3 - optional PDU) in an IT room. The PDU should supply input voltage ranging from 200V to 240V AC. As stated above, the circuit that the PDU plugs into should provide 30 Amps that is not shared by any other device.




Before beginning receptacle installation, consider the following: